Simple calculation method for fresh air volume and exhaust air volume in workshop

Simple calculation method for fresh air volume and exhaust air volume in workshop

Fresh air volume calculation

New air volume calculation method

Calculated by the number of people in the room: (applicable to divided, multiple small rooms)

Qm=N ×qm

N—number of people; (the number of people per unit area can be calculated according to the floor area ratio of the unit area, ie the number of people = area × 0.8)

Qm—new air volume, unit: m3/h;

Qm—The amount of fresh air required by each person (usually calculated by 30 to 50 m3/person per person).

New air volume calculation method 2

Calculated as a percentage of fresh air in total air supply:

Q fresh air volume = total Q delivery × 10 ~ 30% (applicable to areas with large areas)

The fresh air volume is 10% to 30% of the total air supply.

Note: The total air supply volume is the sum of the air supply volumes of multiple air conditioners that carry the cold (heat) load in the air conditioning area.

Exhaust air volume calculation

Exhaust air volume calculation method

Calculated by the number of air changes in the room: (applicable to split, multiple small rooms)

Q exhaust air volume = N × V

N - room air exchange times

V—room volume

Room type

Air exchange times

Room type

Air exchange times

1

bathroom

10 times / h

6

meeting room

12 times / h

2

bathroom

8 times / h

7

restaurant

10 times / h

3

restaurant

10 times / h

8

hall

5 times / h

4

Large dining hall

8 times / h

9

KTV private room

10 to 15 times / h

5

public toilet

15~20 times/h

10

bar

Exhaust air volume calculation method 2 (applicable to areas with large area)

Calculate 80 to 90% of fresh air volume according to exhaust air volume

Q exhaust air volume = Q fresh air volume × 80 to 90%

Case

1. A KTV entertainment venue, the ceiling of the room is 2.8m high, with 50 rooms, each room has an area of ​​28m2. Calculate the total new and exhaust air volume, and select the corresponding new and exhaust fan.

Calculated as follows:

Q new = 20 × 50 × 50m3 / h = 50000m3 / h

Q row = 28 × 2.8 × 50 × 15m3 / h = 58800m3 / h

5 BFP-10D for new fans

The exhaust fan uses six 10000m3/h fans.

2. The total air-conditioning area of ​​a shopping mall is 10000m2, and the unit load is 150w/m2. Calculate the total new and exhaust air volume, and select the corresponding new and exhaust fan.

Using the second calculation method

1. First calculate the air conditioning cooling load of the entire shopping mall, and select the variable air volume air conditioning unit;

2. Calculate the total air supply volume from the selected variable air volume air conditioning unit;

3. Calculate the fresh air volume according to the total air supply volume;

4. Calculate the exhaust volume according to the percentage of exhaust and fresh air.

Metal Chest Of Drawers

A metal locker-style dresser is a piece of furniture with several drawers for storing clothes or kids toys or for home office storage.
The drawer dresser is made of cold-rolled steel sheet with high-quality powder-coated, with several drawers providing plenty of storage.
You might have a dresser in your bedroom that's full of sweaters. Select from a 3-drawer chests, 5 drawer chests and more, depending on the space available in your room.
As you come to a manufacturer, every styles, sizes and colors of locker style chests are available to meet your needs.
You can assembly the dresser with drawers on your own per an assembly video.
You can match a metal locker end table.
What are you waiting for? Take action now!

Metal Chest of Dresser,Metal Locker Dresser,Metal Dresser for Sale

LUOYANG SHIDIU IMPORT AND EXPORT CO., LTD , https://www.shidiucabinetes.com

Posted on